Prosonic FDU80F

Produktbild av: Prosonic FDU80F

This product is no longer available.

Please check new generation in the section predecessor / successor or contact your local Endress+Hauser entity.

Funktioner och specifikationer

Tillbaka

Details

  • Mätprincip

    Ultrasonic

  • Characteristic / Application

    Separated version with field housing and control room instrumentation

  • Supply / Communication

    4-wire (HART, Profibus DP, RS 485)

  • Accuracy

    +/- 0.2 % of set measuring range

  • Ambient temperature

    -40 °C ... 95 °C
    (-40 °F ... 206 °F)

  • Process temperature

    -40 °C ... 95 °C
    (-40 °F ... 206 °F)

  • Process pressure absolute / max. overpressure limit

    0,7 bar ... 4 bar abs
    (10 psi ... 58 psi)

  • Main wetted parts

    ETFE

  • Process connection

    G / NPT 1", DN80 / 100,
    ASME 3" / 4"

  • Process connection hygienic

    3A certification

  • Blocking distance

    0.3 m (1 ft)

  • Application

  • Max. measurement distance

    5 m (16 ft)

  • Communication

    Transmitter:
    4 ... 20 mA HART
    Profibus DP
    RS485

  • Certificates / Approvals

    ATEX
    CSA
    FM
    TIIS
    3A

  • Components

    Transmitter:
    FMU860 / FMU862

  • Successor

    FDU91F

  • Application limits

    Nozzle min. DN80 / 3"

    Lots of obstacles:
    Check stilling well / sonic guide tube

    Thin foam layers / big bubbles:
    Use stronger sensor

    Strong build up / condensation:
    Ask Endress+Hauser

    Take notice of range diagram

  • Mätprincip

    Ultrasonic

  • Characteristic / Application

    Separated version with field housing and control room instrumentation

  • Supply / Communication

    4-wire (HART, Profibus DP, RS 485)

  • Accuracy

    +/- 0.2 % of set measuring range

  • Ambient temperature

    -40 °C ... 95 °C

  • Process temperature

    -40 °C ... 95 °C

  • Process pressure absolute / max. overpressure limit

    0,7 bar ... 4 bar abs

  • Main wetted parts

    ETFE

  • Process connection

    G / NPT 1",
    DN80 / 100,
    ASME 3" / 4"

  • Process connection hygienic

    3A certificate

  • Blocking distance

    0,3 m

  • Max. measurement distance

    2 m

  • Certificates / Approvals

    ATEX
    FM
    CSA
    3A

  • Components

    Transmitter
    FMU860 / FMU862

  • Successor

    FDU91F

  • Application limits

    Take notice of range diagram

Dokumentation / manualer / programvara

Tillbehör / reservdelar

Nr
Order code
Specification
  • Ersättare