Conductive
Point level detection
Pump Protection FTW360

Pump Protection FTW360 ©Endress+Hauser

Compact flush-mounted probe

The FTW360 is made for detection of liquids on the suction side of a pump for dry run protection. It operates in all conductive liquids, sludges and pastes that do not form an insulated build-up on the wall of the piping (e.g. oil film). The unit is also suitable for minimum or maximum detection in tanks.

  • Fördelar

    • Simple and reliable solution also for adhesive or viscous products

    • Cost-effective probe for conductive liquids

    • Universal electronics for AC and DC voltages

  • Applikationsområde

    For detection of liquids on the suction side of a pump for dry run protection. For conductive liquids, sludges and pastes that do not form an insulated build-up on the wall of the piping (e.g. oil film). For minimum or maximum detection in tanks.

    • ...

Funktioner och specifikationer

Tillbaka

Details

  • Mätprincip

    Conductive

  • Characteristic / Application

    Compact limit switch for pump protection,
    Active build-up compensation,
    Flush mounting

  • Specialities

    CIP suiteable

  • Supply / Communication

    21V ... 253V AC
    20V ... 200V DC

  • Ambient temperature

    -20 °C ... 60 °C
    (-4 °F ... 140 °F)

  • Process temperature

    -20 °C ... 100 °C
    (-4 °F ... 212 °F)

  • Process pressure absolute / max. overpressure limit

    Vacuum ... 10 bar
    (Vacuum ... 145 psi)

  • Min. conductivity of medium

    10 µS/cm

  • Main wetted parts

    1.4571, PTFE

  • Process connection

    G3/4

  • Communication

    Relay

  • Application limits

    Observe minimum medium conductivity

Dokumentation / manualer / programvara

Tillbehör / reservdelar

Nr
Order code
Specification
  • 20
    • Nr 20 Order code 52002593

      Cover F6 Alu, high, gasket

      O-ring EPDM. Usage: housing F6, aluminium.

    • Nr 20 Order code 52002594

      Cover F10 PBT, high, gasket

      O-ring VMQ. Usage: housing F10, Polyester.

  • 30
    • Nr 30 Order code 52002590

      Electronics FEW24 AC/DC

      21-250VAC/20-200VDC. Usage: FTW360.

  • 50
    • Nr 50 Order code 52002589

      Sensor FTW360, gasket, SS

      G3/4, 316Ti. Usage: FTW360.

    • Order code 210808-1000

      Weld-in adapter G3/4, O-ring 316Ti

      Material: 316Ti + O-ring, FKM Viton.

  • Föregångare